K&D Factory Service Inc. has serviced commercial refrigeration & commercial kitchen equipment in York PA since 1945.

Call us now at: 1-800-932-0503 or check out why commercial kitchens turn to K&D Factory Services for our top-rated commercial cooking equipment, parts and repair needs in York PA.

Local Reviews
for York, PA



Service C.

Service C.

Found Frozen Drink Machine center bowl leaking down over gear motor, talked with Carrie at Volrath tech support and they are sending a new motor and shaft seal to the York shop. 9/30/19 Replaced shaft, seal and motor on middle bowl (supplied by Volrath), unit is working properly at this time.

Near Kent Rd, York, PA 17402
Service C.

Service C.

came in and replaced digital thermostat on holding cabinet. I had to wait for the unit to cool down so the customer can switch his food to other hot box since he was using this unit. put new thermostat in and tested the the unit. the thermostat is displaying accurate temp. also notice that this unit needs a new door gasket. will order new door gasket and return. 2=METRPC06-916D=DOOR GASKET 9-17-19 replaced top and bottom door gaskets. tested, sys ops okay.

Near Country Club Rd, York, PA 17403
Service C.

Service C.

Arrived at location. Met with Alan. Removed all Coffee equipment on list.

Near Edgecomb Ave, York, PA 17403
Service C.

Service C.

Walk-In Freezer Unit was going off on high head. Condenser coils need cleaned. Cleaned both walk ins. head pressure is good now.

Near E Market St, York, PA 17402
Service C.

Service C.

Call Out for SCT Ice Machine, Had bin full. Light on but bin was empty. Bin switch is bad. we need to order Monday morning. 6/10/19 Replaced bin switch. waited for unit to make 2 batch of ice. tested, bin switch working properly. unit is working properly and making ice for now. Customer said that the water filter is leaking water and he wants us to replace it for them. FresH2O water filter cartridge #9320-1002

Near Arsenal Rd, York, PA 17404
Service C.

Service C.

Checked Convection Oven unit out. found burners dusty. cleaned. secured burner manifold. found needs probe, timer, heat light. will order. 6-7-19 Replaced timer, heat light, temp probe and temp control board. Found new heat light bad and will order new one. Tested calibration.

Near S Queen St, York, PA 17403
Service C.

Service C.

Turned Convection Oven on and found would not turn on. found door switch sticking. lubed switch. let heat up, let cycle a few times. found okay.

Near Loucks Rd, York, PA 17408
Service C.

Service C.

Manager said ice bin unit was full of water yesterday. Bin was clear but still blew out drain lines with nitrogen.

Near Carlisle Rd, York, PA 17404
Service C.

Service C.

Found Dishwasher hose off at back of machine. was able to reinstall hose so customer can use. will order new hose and fitting. 2/6/19 Was unable to get unit apart will reschedule at later time. 2/7/19 Installed vent and hose ran unit tested, okay, no leaks

Near Memory Ln, York, PA 17402
Service C.

Service C.

Found Walk-In Freezer evaporator iced up and fans not working, Thawed evaporator with water and narrowed down fan problem to defrost termination switch by jumping it out, Picked up switch locally and replaced then found one evaporator fan motor bad and replaced it from truck stock, unit is working properly at this time.

Near Roosevelt Ave, York, PA 17408
Service C.

Service C.

Found Ice Machine water distribution plate broken at all four screws causing ice thickness probe to be to close to evaporator and not stay in a consistent position, will order part from United York. 12/21/18 Replaced evaporator top molding and ran ice machine for 3 batches of ice, unit working properly at this time but impeller on pump motor is making a rattling noise and customer would like it replaced, part is on order at United York

Near Poplars Rd, York, PA 17408
Service C.

Service C.

Found Reach-In Cooler unit compressor not running when I arrived, Checked power to compressor and had none, Traced back to thermostat and jumped thermostat and found thermostat to be bad, Replaced thermostat and unit is up and running properly.

Near E Market St, York, PA 17402
Service C.

Service C.

At location owner stated that his oven keeps shutting off and will not get to temp. I tested unit and while at the location unit worked fine. The owner told me that he heard clicking at the module and wanted to replace it. I replaced module and unit is working well.

Near Roosevelt Ave, York, PA 17408
Service C.

Service C.

Found small belt is caught on cross-member that broke, will need to remove belt and weld bar, fix links and replace bushings, will give estimate. 11/27/2018 Found several broken welds in conveyor frame and both belts with damaged areas. Removed conveyor assembly and transported to shop to properly repair. 11/27/2018 Returned conveyor to customer and installed, unit is in operation.

Near Loucks Rd, York, PA 17404
Service C.

Service C.

Walk-In Freezer Unit was low on gas. Filled receiver to 80% and leak checked. Found green leak dye around TXV valve. Could not pin point leak with bubbles so I rebrazed all welds and tightened all areas around the valve.

Near E Market St, York, PA 17402
Service C.

Service C.

Found hot surface ignitor bad on Broiler. will have to order. 9/7/18 Replaced ignitor and installed updated flame sensor, cleaned pilot, ran to temperature, found ready to use.

Near Roosevelt Ave, York, PA 17408
Service C.

Service C.

Bunn Tea Machine going into ign failure, found flame sensor dirty, removed and cleaned, tested okay.

Near S George St, York, PA 17401
Service C.

Service C.

Verified customer concern. Found no power to thermostat on HVAC System. Checked breakers, none tripped. Checked unit 209-212 vac across all phases, control board not lit, unit not running. Checked transformer, 211 vac in but no secondary power. Reset transformer, board powered up. Allowed both stages to start, both stages started and unit began cooling. Reset time & date on thermostat. (date was off by 1 day, which means this went down sometime yesterday). No issues found on why transformer overload tripped. There could be an intermittent board going bad, a coil starting to go bad or could have been caused by power surge due to weather they have been having. If this happens again, may need to install inline fuses to isolate. Unit is working properly and cooling at this time.

Near Kenneth Rd, York, PA 17404
Service C.

Service C.

Found Blended Ice Machine off. Manager showed me the pieces in drink. They were opac and fine chars. Checked pitcher, did find lip of pitcher has pieces broken off and a crack on side . Took pictures of pitcher. Removed ice from bin. Did not find any foreign objects in ice. Removed ice bin, found in-tact. Reinstalled ice bin. Manager ran weekly cleaning. Filled ice bin. Ran several drinks found no shards. Unit ready to use.

Near S Queen St, York, PA 17403
Service C.

Service C.

Condensing unit for Walk-In Cooler was very hot. Condenser fan motor was changing speeds, causing hp to raise. Called United York, they will call back and let me know if they have one. Told manager to put a fan on unit to help for tonight. 06/26/18 Went to get parts. installed new condenser fan motor. Started unit and speed for the fan is correct.

Near Springwood Rd, York, PA 17403
Service C.

Service C.

Walk-In Freezer - Re-insulated the suction line on the roof and above the walk in. I also insulated the sprinkler lines which were sweating and dripping on the box. Sealed electrical penetration behind evaporator. Top of the walk in should now remain dry.

Near S Queen St, York, PA 17402
Service C.

Service C.

checked unit found switch loose but working okay tighten switch. found power to motor. will pick up new capacitor and see if that will help, if not motor is bad. 5/16/18 installed new capacitor for lift motor ran unit working okay

Near Pine Grove Rd, York, PA 17403
Service C.

Service C.

Door sweep was loose and rubbing. Will order a new one. Sent deb info *****mileage and travel on work order # 156364**** 5/7/18 installed new door sweep

Near Country Club Rd, York, PA 17403
Service C.

Service C.

Machine was go in going off on high head pressure due to some bubble wrap dropping behind unit. Watched one freeze cycle unit working fine. Found temp sensor T3 reading wrong, will order and return. 3/30/18 Installed new T-3 sensor, checked for proper reading. Clear alarms.

Near Pine Grove Rd, York, PA 17403
Service C.

Service C.

Under Counter Refrigerator Unit was warm and evaporator coils were iced up. Put unit in defrost and heaters worked and timer. Will return tomorrow to check charge and operations. 3/20/18 Turned unit back on. condenser was hot . Blew out and unit was down to 5 degrees when I left.

Near Pine Grove Rd, York, PA 17403