Upon arrival Walk-In Cooler unit was running, found all 3 fan motors seal were bad and leaking oil. Talked to Martin and explained what I found and he agreed that I was to sourc the parts locally. Returned to site with parts, removed all faulty fan motors and installed new one. Reassembled and tested unit. Unit is working properly now.

Near Centre Square, Easton, PA 18042
Service C.

Service C.

Upon arrival Reach-In Freezer unit was running, cabinet temperature was @15F. Customer stated the temp has gone up 6 degrees since last hour. Troubleshot and found the condenser coil has completely cover with flour and grease. Cleaned the coil and started the unit and checked unit's proper operation and found unit was low on charge. Top off the charge for the customer and watched unit cooling down to temp. Unit is working okay at the moment. **Told customer due to the condition of the unit, he may need to buy a new unit in the future. ** THEY ARE BUSY WHILE I WAS ON SITE, THEY KEEP OPEN AND CLOSE THE DOOR, CAN'T STAY AND WATCH UNIT SATISFIED ON SETPOINT.

Near Mort Dr, Easton, PA 18040
Service C.

Service C.

Removed Range and fryer gas hose and installed customer supplied gas hose and waited till singer brought in the new range. Hooked up gas and turn on and lit pilots and burners on range top. Lit pilot in oven and set oven to 300° F and cycle 3 times . Temps ok. Range is in service .. Also helped move some equipment in and out and help peel off the laser film. Ready for service .

Near Sullivan Trail, Easton, PA 18040
Service C.

Service C.

Upon arrival Reach-In Freezer unit was @ 42F. Checked evap coil and found whole coil was iced up. Manually put unit in defrost cycle and found compressor is not shutting off. Troubleshot and found the compressor contact inside the controller was stuck closed, and causing the compressor to run all the time.The defrost heater is working properly, and all fans are running. Talked to manager and explained what I found, order part and return for repair per Martin. ** Explained to customer will need to do more diagnosis on the unit once new controller is installed. ** 12/31/19 Returned to replace the temperature controller. Removed the old temperature controller and installed the new controller. Modified the necessary wire connection per installation instructions. Started the unit and checked for proper operation, unit is cooling down to temp. Tested the unit's defrost cycle operation, it is working properly now. Heater is pulling 5.78 amp. Compressor is pulling 12.1 amp. Explained

Near Centre Square, Easton, PA 18042
Service C.

Service C.

Garland range LEFT oven pilot goes out - arrived on site to check Garland range, left oven. proceeded and disassembled left oven pilot burner. checked and cleaned gas pilot orifice. rerouted thermocouple from under oven burner to right side access connecting to pilot burner. relit pilot, pilot remaining lit. brought oven into operation. found thermostat out of adjustment. recalibrated thermostat, set at 350°, oven temperature averaging 353°. oven in service.

Near Northampton St, Easton, PA 18042
Service C.

Service C.

Upon arrival Reach-In Freezer unit is running okay, food inside the freezer was frozen. Started PM on the unit, checked condenser coil, coil is dirty. Cleaned the coil with nitrogen gas. Checked evaporator coil, coil is clear. PM is completed.

Near Spring Garden St, Easton, PA 18042
Service C.

Service C.

Looked over Garland range RIGHT side salamander found right burner and right gas valve bad will order and return. 9/25/19 Removed right burner and installed new. Also changed the valve as well. Lit pilots. Both lit okay. Turned on both burners. Both lit okay and are staying lit. Back in service.

Near Northampton St, Easton, PA 18042
Service C.

Service C.

arrived at location for leaking dishwasher which is an ongoing issue called champion spoke to Mark he said to either replace the gasket again the shaft seal, bearing housing and put a lot of plumbers putty not only on the bolts themselves but in the holes as well. will order parts for anticipation and plumber's putty and will return got all part numbers from Mark west in to see if someone from maintenance would sign but at the time no on was available.. unit not in service. 9/9/19 Installed parts. Turn on. Let run a while. No leaks from rack drive housing or vacuum breakers. Maintenance said there were no leaks since the last time I was here. Back in service.

Near Walnut St, Easton, PA 18042
Service C.

Service C.

found right front of griddle separating and flame from burner going to that spot. not repairable. unit operational, job complete. recommended using that side for holding.

Near Northampton St, Easton, PA 18042
Service C.

Service C.

Spoke to customer and they said the Tea Brewer unit was brewing weak. Checked batch size, re-calibrated to quarts, and checked operation of thermostat and elements. found 13 amps, brewed batch and had customer check strength. Customer okay-ed batch. Unit is operating correctly at this time.

Near Nazareth Rd, Easton, PA 18045
Service C.

Service C.

Found 3 pilots out on the range top. Replaced the center thermocouple on the front burner. Cleaned and adjusted the left rear and right rear pilots. All stay on now. Lit the griddle pilots and both stay lit. Both oven pilots are on. unit is in service .

Near Washington St, Easton, PA 18042
Service C.

Service C.

Checked CLE Steamer unit, found terminal block in top cavity shorted. Disconnected all neutrals and wire muted together. Turned unit on, no shorts to ground. unit filled reset lite came on. and unit fired, came to 13 psi and cycled both cabs steamed. Unit operational but requires parts. Will obtain terminal block and return. Top cab needs timer. 9/25/18 Installed terminal block and timer. Turned on. Filled and heated to steam. Set timers. Timed down and buzzed. Back in service.

Near Riverside Cir, Easton, PA 18045
Service C.

Service C.

Arrived at customer location for install Pitco Fryer-Gas unit, didn't have gas line hose. Told customer and they guided us to another building where we had to take the hose off of an old unit. Attached hose to new equipment, tested with soap and water for any gas leaks. No leaks. Also lit pilots and tested burners, pilots and burners both light up, after turned off pilots and burners, unit is ready for use

Near Sullivan Trail, Easton, PA 18040
Service C.

Service C.

Found Warmer intermittently tripping gfi outlet, Chef says switch doesn't always work and trips gfi. Will order switch and light. 5/17/18 Follow up- Replaced power switch and indicator light. Unit heating properly.

Near Newlins Rd W, Easton, PA 18040
Service C.

Service C.

Turned on. No power to the fill valve. The fill LED light does not come on at start but the heat LED is on. Probes are clean. Replaced board and turned on. Unit Fills and beats to steam. Back in SERVICE.

Near Chipman Rd, Easton, PA 18045
Service C.

Service C.

Prep Table Compressor not starting. Condenser blocked with dust. Cleaned coil. Compressor seized. Will quote replacement. 1/12/18 Replaced compressor. Pulled vacuum and recharged. Unit cooling properly.

Near Riverside Cir, Easton, PA 18045
Service C.

Service C.

One burner not installed correctly. Reinstalled. Right oven thermostat failed. Customer wants quote. 12/8/17 Replaced right oven thermostat. Unit working properly.

Near Bushkill Dr, Easton, PA 18042
Service C.

Service C.

Took top cover off and found nut on center shaft had loosened up. Tightened up and ran. Unit locked up in 3rd. Took gearbox cover off and found scrapings from upper spacer got into slow speed assembly. Cleaned out chips. Reassembled. Ran in all 3 gears. Unit ready to use.

Near Kesslersville Rd, Easton, PA 18040
Service C.

Service C.

Shower handle button broke on Combi Oven. 7/26/17 Need new handle. Also need door gasket. Will obtain and return. 8/11/17 Installed new door gasket and sprayer handle. No leaks. Back in service.

Near Freemansburg Ave, Easton, PA 18045
Service C.

Service C.

Found transformer putting 134 out, 212 in. Also water level board not responding to power in. Will obtain parts & return. 8/22/17 Installed new board and transformer. Turn on and light blinks on board. Troubleshoot further and found contactor shorted. Need new. Will obtain and return. 9/7/17 Installed new contactor. Turn on. Heats. 9.75 amps/leg. Came to steam. Set timer and it timed down & sounded. Back in service. Kitchen personnel verified operation.

Near Washington St, Easton, PA 18042
Service C.

Service C.

Thermostat failing. Will order & return. 7/27/17 Replaced thermostat. Turned unit on. Unit heats and cycles. Also changed cartridge on steamer. Old one was clogged

Near Riverside Cir, Easton, PA 18045
Service C.

Service C.

Door frame heater failed. Gasket torn. Will order heater and gaskets. 6/28/17 Replaced walk in door gaskets. Will have to reorder door frame heater. Wrong one ordered. 7/11/17 Installed door frame heaters. Removed ice buildup on door.

Near Fairview Ave, Easton, PA 18042
Service C.

Service C.

Found HSI glowing. Low. 9A. Ignitor bad. Will obtain & return. 5/31/17 Installed ignitor. Glowed. No light, had no power to gas valve. Replaced module and tested okay. Unit operational job complete.

Near William Penn Hwy, Easton, PA 18045
Service C.

Service C.

Pulled unit from line and disassembled and found one wire has come off the main switch. Wire was not long enough. Lengthen wire and now unit works. 7.10 amp total. Lights work and element works. Assemble and put back in service. Unit okay.

Near Riverside Cir, Easton, PA 18045
Service C.

Service C.

Pulled probes on both generators and all 4 were limed up. Cleaned all & test. Not filling water. Found filters have no water going through. Zero pressure. Replace main filter cartridge and scale stick and flush for 5 min. Power on and both generators now fill. Have 20 psi while filling. Both now fill and heat. Allow to reach ready and test top & bottom. Found steam leak for bottom steam hose and both motors do not work. Top replace fan motor and fan it runs now. Need top and bottom steam hose, motor & fan for bottom cabinet. Will order and return. 4/6/17 Removed parts from used unit per customer. Blower motor, blower wheel, hoses. Replaced on another unit. Power on. Allowed to heat to steam. Both compartments steam. Top door gasket leaks. Blower motors both run. Steam good. No leaks. Back in service.