Mark B.
Mark B. Checked in
Arrived at location on 3/1/23 - -Checked over unit. Found during pm a few issues that will need corrected. One of the issues including water leak from drain hose. Disabled water fill valve to prevent generator fill so it doesn’t leak into electrical components. Will return with parts. Returned to location on 3/10/23 - Replaced filters, drain hose and drain pipe with couplers. Tested unit in all modes and found all ok at this time with no leaks.
Montoursville, PA 17754
Mark B.
Mark B. Checked in
Arrived at location on 6/29/22 - Checked over unit, found all controls unresponsive, opened up and found no voltage at terminal block. Found unplugged. Plugged in and breaker immediately tripped. Unplugged and reset breaker. Used meter and found hot and neutral shorted to ground, made further inspection of wiring. Found one wire with damaged insulation had shorted directly to the frame. Cut back damaged portion of wire and spliced together with ceramic wire nut. Checked with meter and verified that nothing is shorted to ground, plugged back in, breaker didn’t trip. Turned on unit and allowed to heat up. Found no other problems, confirmed unit working correctly at this time.
Montoursville, PA 17754
Mark B.
Mark B. Checked in
Arrived at location on 2/11/22 - Checked over unit, found burner flame is decent, flame is blue with a few orange tips once in a while, set thermostat to 350F, when heat indicator went out the temperature was only 226F, set thermostat to 500F, only came up to 346F, thermostat has failed and will need to be replaced. Returned to location on 2/22/22 - Removed side panel, removed failed thermostat, installed new thermostat, turned on unit, set to 350F, heated up to set point, temperature is within range, closed up unit, confirmed unit working correctly at this time.
Montoursville, PA 17754
Mark B.
Mark B. Checked in
Arrived at location on 7/13/21 - Found vat empty, with large amounts of debris in valve, cleared debris and cycled valve found ball valve is misaligned and will need valve and actuator replaced. Cycled shut and verified oil leaks. Returned to location on 7/16/21 - Replaced drain and actuator for right vat, ensured proper cycling filled and verified no leaks, let heat to temp cleared debris in bottom. Unit is operating correctly at this time.
Montoursville, PA 17754
Ashley B.
Ashley B. Checked in
Arrived at location on 5/13/21 to perform service on fryer. Replaced a part, tested and was in working order.
Montoursville, PA 17754
Libby D.
Libby D. Checked in
UNIVEX MIXER - 4-14-21 John S-checked over unit. found belt bad on motor and found its chewed up from a bad pulley. will order and return. 4-21-21 Heath N-Replaced pulley and belt, tested unit found to run smoothly with no noise at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
Found breaker for wall outlets behind fryers and oven tripping, found cause was defective plug for pressure fryer. Installed new plug turned on let heat found okay at this time. **Travel Charges Billed on wo# 222962**
Montoursville, PA 17754
Service C.
Service C. Checked in
Found drain line fell off bottom RAG Combi Oven unit. secured units drain and found leak to stop. found no other issues at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
Delivered LAK Plate Heater/Dispenser unit, verified 208v supplied. old plug was burnt, got new plug. Installed and turned unit on. Found okay at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
MAN Ice Machine: Removed water distribution components, physically cleaned components, reinstalled components, performed physical cleaning of interior, performed chemical cleaning, performed chemical sanitization, put unit into ice, allowed unit to drop batch of ice, tested operations, confirmed unit working correctly at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
Found Booster Heater Dishwasher unit idle with wash temp at 170. Ran rack through found rinse temps did not rise above 120 and booster never kicked to heat. Checked over booster found limit tripped. Reset and found contactors to latch and begin heating. Found 8 amps on all legs. let heat until satisfied. Ran multiple racks through unit. Found rinse temp at around 200 degrees. Lowered thermostat and ran racks through. Found rinse temp at 190 degrees every time. Unit is operating correctly at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
Found Steam Table left burner with large yellow flame and soot covering burner area. Adjusted shutter to achieve normal blue flame. Cleaned as much soot off as possible from area found good flame once shutter was adjusted and soot removed. Unit is operating correctly at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
Performed physical cleaning of ice machine, performed chemical cleaning of ice machine, performed chemical sanitation of ice machine, put unit into freeze cycle, allowed unit to drop ice, tested operations, confirmed unit working correctly at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
Found Reach-In Cooler unit with box temperature of 26°f. with compressor still running. Found temperature control stuck closed. Freed temperature control and set to warmest setting. Box temperature holding at 33°. Will need temperature control replaced. 11/22/19 Removed temperature control, installed new temperature control, allowed unit to come down to temperature, temperature holding at ~34F, tested operations confirmed unit working correctly at this time
Montoursville, PA 17754
Service C.
Service C. Checked in
Ran Dishwasher unit through startup, found wash tank heaters not energizing. Found hi limit tripped. Reset high limit and ran diagnostics on each function. All systems passed. Ran unit through several cycles. Machine drained and operated normally. Found detergent leaking from rear of unit around detergent chute. Will order new gasket and return. 10/28/19 Removed failed chute gasket and replaced. While here unit exhibited draining issue from original call. Checked over unit found draining is not the issue. The unit is actually over filling the booster tank causing water to over fill wash tank through the detergent chute. will order new fill valve. 10/30/19 Replaced valve, turned on checked for leaks found okay, allowed to fill and heat found okay, ran through cycle found okay, drained unit found to drain properly. Unit is operating correctly at this time. Final temps were wash 160 and rinse 180.
Montoursville, PA 17754
Service C.
Service C. Checked in
Found Ice Machine unit not energizing in ice mode. Found energizing in wash mode. Checked switch, found okay. Found bin switch actuator installed backward. Removed actuator, reinstalled, energized unit and checked operation - unit operating normally at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
Removed Reach-In Cooler failed condenser fan motor, door magnet and door switch and replaced. Energized unit and checked operation. Unit operating normally at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
Removed Combi Oven latch cover plate and inspected latch mechanism. Found spring broken. Parts not sold separately, Needs left hand latch assembly. 5/15/19 Removed failed latch assembly and replaced. Checked operation unit operating normally at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
Found Electric Oven door hinge bent. Attempted to bend piece back. Was able to refasten hinge onto unit and door is operable at this time. Will order new hinge and return to replace. 2-27-19 Removed failed hinge and replaced.
Montoursville, PA 17754
Service C.
Service C. Checked in
Found Dishwasher unit with very little water flow to tank when filling. Took over 20 min. to fill and went into low water error. Removed solenoid valve and cleaned inlet strainer. Removed strainer and cleaned screen. Unit filling in 5 min. now. Strainer and solenoid valve corroded internally and should be replaced.
Montoursville, PA 17754
Service C.
Service C. Checked in
Removed top steamer failed door seal, drain valve and door latch assembly and replaced. Unit operating normally at this time. **Travel Charges Billed on wo# 167076**
Montoursville, PA 17754
Service C.
Service C. Checked in
Found MFO Steamer unit on with Door gasket leaking and drain valve stuck shut. Will order parts and return to replace. **Travel Charges Billed on wo# 167076**
Montoursville, PA 17754
Service C.
Service C. Checked in
Found BLO Combi Oven unit off. Turned on and found fan would not spin, pushed fan, it started to turn, will need capacitor. 8-8-18 Removed failed capacitor and installed new capacitor. Energized and checked operation. Fan still would not start. Checked capacitor micro ferrods, found 5.09uf on a 5th capacitor. Checked voltage to motor, found. Correct. Unit needs new blower motor and blower wheel. 8-15-18 Removed blower wheel and failed motor. Replaced motor and blower wheel, energized and checked operation. Found motor would spin without blower wheel Installed. Checked frequency drive, found under load driver will not select proper frequency to run motor. Driver will need replaced. 8-24-18 Found unit off. Removed side cover replaced old inverter drive kit. Started unit, brought unit to operating temp. Tested blower at all speeds. Found okay. Unit is operating normally at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
Checked operation on SBR Range and the unit was trying to light but the igniter is bad. It was receiving 120 volts but wouldn't lite up. When I moved the unit it tripped the breaker from the cord being damage. The staff is running over it with the wheels and spreading it. I replaced the cord and put the unit back together but we will need to order parts and return to install. 6-18-18 Replaced igniter and tested, all okay at this time.
Montoursville, PA 17754
Service C.
Service C. Checked in
Checked over microwave oven unit, found fan not blowing. Removed fan and checked. found locked up tried to free but was stuck. Replaced with new, tested okay. Had customer run with product found unit okay.
Montoursville, PA 17754

Planned Maintenance

A planned maintenance agreement can keep your equipment running longer than the factory warranty. Reduce cost, downtime and have your equipment running at top performance when you need it most.

We Do It Right The 1st Time!

See what our customers think about our service!

Great service Very courteous polite and knowledgeable The Gardens At Stroud Stroudsburg
Super Guys! The K & D Team of repairman are super!. always courteous, friendly and get the job done right! Answer my questions and never a surprise cost. Dunmore Health Care Center Dunmore
Maintenance Supervisor Shawn is a good Devoted Service Tech from your Altoona Offfice Steve Long is always a great help when i call him Mount Union School District Mount Union
Read More